CTE-5201 1 Installation and Operation Guide
Mounting the Thermostat
1. Ifthethermostatis
lockedonthebackplate,
turnthetwohexscrews
(inthetwo outermost
holes)inthebackplate
CLOCKWISEuntilthey(just)clearthecover.
Swingthethermostatupandawayfromthe
backplatetoremoveit.
CAUTION
To prevent damage to the board, do not insert
a screwdriver into any holes other than the two
outermost holes. To prevent mounting screw heads
Installation and Operation Guide
Electronic Room Thermostat (Modular)
CTE-5201
Mounting
Rough-in Preparation
For optimum temperature sensor performance, the
thermostat must be mounted on an interior wall
and away from heat sources, sunlight, windows,
air vents, and air circulation obstructions (e.g.,
curtains, furniture).
Completerough-inwiringpriortoinstallation:
• Routethecablefromthethermostatlocationto
theactuatortowhichitwillconnect.SeeWiring
on page 2.
•
Ifneeded,installtheHMO-1161mounting
backplate.SeeAdditional Information on page 4.
from touching the circuit board in the thermostat, use
only the mounting screws supplied by KMC Controls.
Using other screws may damage the thermostat. Do
not turn screws in farther than necessary to remove
the cover.
2. Routethecablethroughthebackplate.
3. Withthehexscrewstowardthe
oor,fastenthebackplatetothe
outletboxwiththesuppliedscrews.
(Thebackplatemountsdirectlyon
vertical2x4inchboxes,butre-
quiresanHMO-1161wallmounting
plateforhorizontalor4x4boxes.)
4. Insertthemodularendofthecable
intothejackofthethermostat.
5. Placethetopofthethermostatoverthetopof
themountingbaseandswingitdownoverthe
hexscrewbrackets.Becarefulnottopinchthe
wiring.
6.
Backthehexscrewsoutofthebackplatebrackets
(counterclockwise) untiltheyengagethether-
mostatandholditinplace.
A
B
C
E F
RJ-12
Modular
Connector
D
Pin 6
Pin 1
Mounting 1
Rough-in Preparation 1
Mounting the Thermostat 1
Wiring 2
Modular to Modular (HSO-22xx Cable) 2
Modular to Leads (HSO-5012 Cable) 2
Operation 3
Turn On Backlight 3
Change Setpoint 3
Start Unoccupied Mode 3
Toggle Between °F and °C 3
Configuration 3
Changing Defaults 3
MAX 3
MIN 3
F/C 3
UNOCC 3
PROP 4
INT 4
Calibration (Temperature Offset) 4
Maintenance 4
Additional Information 4
Pin 1 and 6 Pin 2 and 5 Pin 3 Pin 4
N/C Common Supply
(14–19VDC)
Output
(2–10VDC)*
*0VDCduringUnoccupiedOmodewhentemperaturestays
above50°F
A
3.25
in.
83
mm
B
5.16
in.
116
mm
C
0.88
in.
22
mm
D
0.38
in.
10
mm
E
2.58
in.
66
mm
F
3.25
in.
83
mm
Vista de página 0
1 2 3 4

Resumo do Conteúdo

Página 1 - CAUTION

CTE-5201 1 Installation and Operation GuideMounting the Thermostat1. Ifthethermostatislockedonthebackplate,turnthetwohexscrews(in

Página 2 - 3/8"

CTE-5201 2 Installation and Operation GuideWiringModular to Modular (HSO-22xx Cable)UseHSO-22xxcablestoconnectthether-mostattoMEP-4x42a

Página 3 - Operation

CTE-5201 3 Installation and Operation GuideConfigurationOperationChanging DefaultsThefactorydefaultseingsare:• Setpoint(Default):70F•

Página 4 - Additional Information

CTE-5201 4 Installation and Operation GuideMaintenanceRemovedustasnecessaryfromholesintopandboom.Cleanthedisplaywithso,dampclo