STE-1454/1455 1 Installation Guide
Installation Guide
Temperature Sensor, Strap-On
STE-1454/1455
Mounting
These models are designed for monitoring uid tem-
peratures in situations where an immersion sensor
cannot be used. Mount the probe in direct physical
contact with the pipe and under pipe insulation.
1. For the STE-1454 (only), mount the included
case (see the diagram) in a suitable location close
to where the probe will be aached to the pipe.
Aach conduit to it as needed.
NOTE: The STE-1455 does not include an
enclosure.
2. From the probe area, remove any pipe insulation
and clean the exterior of the pipe to ensure good
contact and heat transfer.
NOTE: For best results, apply thermal conductive
compound to the pipe underneath the
sensor.
3. Place the sensor probe in direct contact with the
pipe and strap the probe to the pipe using metal
pipe straps or cable ties.
4. Any extra lead length can be wound around the
pipe for extra security.
5. Wrap, or replace, insulation around the sensor to
reduce the eect of ambient air temperature.
Mounting 1
Connections and Wiring 1
Configuration 2
Maintenance 2
Specifications 2
More Information 2
Important Notices 2
4.56”
115.8 mm
2.110”
53.6 mm
2X Ø 0.850”
4.24”
107.7 mm
2.04 ”
51.8 mm
4.0”
101.6 mm
Metal Enclosure
8X Ø 0.875”
2.10”
53.3 mm
5.0 feet
1.524 m
3.320“
84.3 mm
Mounting Holes (X2) Ø 0.200”
5.0 feet
1.524 m
Plastic Enclosure
0.25“
6.35 mm
304 Series
S/S Probe
2”
50 mm
0.25“
6.35 mm
304 Series
S/S Probe
2”
50 mm
Connections and Wiring
1. For the STE-1454, feed the wire leads through
the hole in the enclosure and secure with the
included grommet.
2. Make connections to the two wire leads with
either bu-splices or solder. Using wire nuts is
not recommended.
NOTE: The two-wire sensor is not polarity
sensitive.
Vista de página 0
1 2

Resumo do Conteúdo

Página 1 - Installation Guide

STE-1454/1455 1 Installation GuideInstallation GuideTemperature Sensor, Strap-OnSTE-1454/1455 MountingThese models are designed for monitoring uid

Página 2 - Important Notices

STE-1454/1455 2 Installation Guide© 2014 KMC Controls, Inc. 717-019-19DKMC Controls, Inc.19476 Industrial DriveNew Paris, IN 46553574.831.5250www

Modelos relacionados STE-1454

Comentários a estes Manuais

Sem comentários