Kmc-controls BAC-8007 Installation Guide Manual do Utilizador Página 28

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 88
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 27
Procedure Detailed steps STE display
3 Set the minimum cooling
setpoint.
This setpoint limits the lowest temperature that a
user can enter as the active setpoint.
1.
Press the or buttons to set the minimum
cooling setpoint. The setpoint will change in
0. increments.
2.
Press the
Set
Point
button to save the setpoint and
advance to the next function.
MIN
68O
4 Set the maximum heating
setpoint.
This setpoint limits the highest temperature a
user can enter as the active setpoint.
1.
Press the or buttons to set the maximum
heating setpoint. The setpoint will change in
0. increments.
2.
Press the
Set
Point
button to save the setpoint and
advance to the next function.
MAX
78O
5 Set the occupied cooling
setpoint.
This setpoint is used as the active setpoint when
the space is occupied.
1.
Press the or buttons to set the occupied
cooling setpoint. The setpoint will change in
0. increments.
2.
Press the
Set
Point
button to save the setpoint and
advance to the next function.
Note: This setpoint can also be changed as
described in the topic Changing the room
setpoint on page 23.
OCCL
74O
Procedure to set the temperature setpoints (continued)
Section 4: Configuring the controllers SimplyVAV
28 Revision E
Vista de página 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 87 88